Chapter 1. Installation 23
Step 3
Run your motor at the resonant speed listed in the Offset Adjust column. Vary the speed
slightly until you find the resonance point.
To initiate motion, type these commands (followed by a carriage return) to the ZETA6104
from the terminal emulator:
MC1 (This command makes the motion run continuously until you issue a !S command.)
Vn (This command sets the velocity to n . For example, V4.66 sets the velocity to 4.66 rps.)
GO (This command initiate motion.)
To vary the speed while the motor is moving, type these immediate commands:
!Vn (This command selects the new velocity of n.)
!GO (This command changes the motorÕs velocity to the new velocity value of n.)
NOTE: To stop the motor during this procedure, issue the !S command.
Re-issue the GO command to resume motion.
Step 4
Adjust the Phase A Offset and Phase B Offset pots for minimum motor vibration and smoothest
operation. Alternate between Phase A and PhaseÊB to find the minimum vibration point.
Step 5
Run your motor at the resonant speed listed in the Balance Adjust column. Vary the speed
slightly until you find the resonance point.
Step 6
Adjust the balance pot until you find the setting that provides minimum motor vibration and
smoothest operation.
Step 7
Repeat steps 3Ð6.
Step 8
Run the motor at the resonant speed listed in the Waveform Adjust column. Vary the speed
slightly until you find the resonance point.
Step 9
Choose the current waveform that provides minimum motor vibrations and smoothest
operation at the speed you selected in step 8. To find the best waveform, compare motor
performance as you select different waveforms using the !DWAVEF command.
Waveform DWAVEF Setting
-4% 3rd harmonic !DWAVEF1 ¬ Factory default
-10% 3rd harmonic !DWAVEF2
-6% 3rd harmonic !DWAVEF3
Pure sine !DWAVEF4 ¬ Do not use if drive resolution (DRES) is set to 200 steps/rev
NOTE: The DWAVEF command setting is NOT automatically saved in non-volatile memory; therefore, if
DWAVEF1 in not adequate, you have to place an alternative DWAVEF setting in a set-up (STARTP)
program. Refer to page 31 for an example.
Step 10
Disconnect AC power to turn off the ZETA6104. Replace the cover over the pots. This
completes the matching procedure.
Step 11
Proceed to the next section to mount and couple the motor.